Ư¡

Hyundai medium voltage metal-clad switchboards with withdrawable
circuit-breaker are of single(1)-Tier or two(2)-tier, factory-assembled and
suitable for rated voltage of 7.2kV to 12kV.
The switchboards have been type tested in accordance with related IEC
regulation.

»ç¾ç
Frame work Formed sheet steel or substantial box-frame
Access Front and rear
Protection degree IP21, IP22, IP32, IP4x
Handrail Front and rear
Power line inlet Bottom or upper part of the rear(upper part, option)
36,000 2,000 ~ 3,000
[HMS-112]

Electrical Characteristics for HMS-112

Rated
voltage
(kV)
Rated 1min
power-frequency
withstand voltage
(kV peak)
Impulse
withstand voltage
(kV peak)
Rated current
(A)
Short-time withstand current
for 1s*
(kA rms) (kA peak)
7.2 20 60 1,250,
2,000
25 63
12 28 75 1,250,
2,000
25 63
Power line inlet         Bottom or upper part of the rear(upper part, option)
36,000         2,000 ~ 3,000

* For duration > 1s, consult us

Cubicle Dimension for HMS-112

Rated voltage(kV) Rated current(A) Width(mm) Depth(mm) Height(mm)
7.2 1,250 650* 1,500 2,450
2,000 750
12 1,250, 2,000 750 1,700 2,450
36,000        

* For duration > 1s, consult us