| Application
for HVF/HAF Type |
| 2nd Shunt Release
with Attachment |
| ¡¤ |
2nd shunt releases are used to open the circuit breaker automatically
with appropriate protective relays or by deliberate electrical or mechanical
action. They are designed for connection to external voltage (AC or DC)
; However, in special cases they may also be connected to voltage transformer. |
| Undervoltage
Release with Attachment |
| ¡¤ |
Undervoltage releases are used to open the circuit breaker automatically
in the event that the operating voltage drops below a specified level.
- Pick up : 75 ~ 85% of rated voltage
- Drop-out : 35 ~ 60% of rated voltage |
| Electrical
Lockout with Attachment |
¡¤
|
The lockout relay is an electromagnetic device actuated by DC or AC voltage
for the voltage independent interlocking of switching devices.
- Pick up : Over 85% of rated voltage
- Drop-out : Below 60% of rated voltage
- Capacity : 25W(DC) / 25VA(AC) |
| Cut-out Switch |
| ¡¤ |
This unit sends signal for the alarm when the circuit breaker is tripped.
|
| Charging Signal for Tripping |
| ¡¤ |
The charging status of closing spring will be indicated by the installation of limit switch.
|
| |
| |
| Application
for HVG/HVF/HAF Type |
| Vacuum
Checker |
| ¡¤ |
The portable vacuum checker can be used for checking the vacuum degree.
Rated input voltage : AC220V
Rated output voltage : AC11kV / 22kV
Dimension : W200 x L350 x H176 |
| Capacitor Trip
Device |
| ¡¤ |
It is recommended that the capacitor trip unit is to be employed for a
trip operation of the breaker when the control source is lost in the AC
control system.
Rated input voltage : AC110V, AC220V
Rated output voltage : DC145V, DC 290V |
| Varistor Module |
| ¡¤ |
When the motor, solenoid and shunt releases are switched in DC circuits,
it is possible for surges to be produced which might cause great damage
to solid-state devices.
By additionally connecting the varistor module to the motor and solenoid,
the damage can be effectively eliminated. |